Model
|
SUN-18K-G05
|
SUN-20K-G05
|
SUN-25K-G05
|
Input Side
|
|||
Max. DC Input Power (kW)
|
23.4
|
26
|
32.5
|
Max. DC Input Voltage (V)
|
1000
|
||
Start-up DC Input Voltage (V)
|
250
|
||
MPPT Operating Range (V)
|
200-850
|
||
Max. DC Input Current (A)
|
26+26
|
||
Max. Short Circuit Current (A)
|
39+39
|
||
No.of MPP Trackers
|
2
|
||
No.of Strings per MPP Tracker
|
2
|
||
Output Side
|
|
||
Rated Output Power (kW)
|
18
|
20
|
25
|
Max. Active Power (kW)
|
19.8
|
22
|
27.5
|
Rated Output Voltage/Range (V)
|
3L/N/PE 220/380V, 230/400V 0.85Un-1.1Un (this may vary with grid standards)
|
||
Rated Grid Frequency (Hz)
|
50 / 60 (Optional)
|
||
Operating Phase
|
Three Phase
|
||
Rated AC Grid Output Current (A)
|
27.3/26.1
|
30.3/29
|
37.9/36.2
|
Max. AC Output Current (A)
|
30/28.7
|
33.3/31.9
|
41.7/39.8
|
Output Power Factor
|
0.8 leading to 0.8 lagging
|
||
Total Harmonics Current Distortion (THDi)
|
<3%
|
||
DC Injection Current (mA)
|
<0.5%
|
||
Grid Frequency Range
|
45~55 or 55~65 (Optional)
|
||
Efficiency
|
|
||
Max. Efficiency
|
98.6%
|
||
Euro Efficiency
|
97.8%
|
||
MPPT Efficiency
|
>99%
|
||
Protection
|
|
||
DC Reverse-Polarity Protection
|
Yes
|
||
AC Short Circuit Protection
|
Yes
|
||
AC Output Overcurrent Protection
|
Yes
|
||
Output Overvoltage Protection
|
Yes
|
||
Insulation Resistance Protection
|
Yes
|
||
Ground Fault Monitoring
|
Yes
|
||
Anti-islanding Protection
|
Yes
|
||
Temperature Protection
|
Yes
|
||
Integrated DC Switch
|
Yes
|
||
Remote Software Upload
|
Yes
|
||
Remote Change of Operating Parameters
|
Yes
|
||
Surge Protection
|
DC Type II / AC Type II
|
||
General Data
|
|
||
Cabinet Size (WxHxD mm)
|
362×527×220 (Excluding Connectors and Brackets)
|
||
Weight (kg)
|
20
|
||
Topology
|
Transformerless
|
||
Internal Consumption
|
<1W (Night)
|
||
Running Temperature
|
-25-65ºC, >45ºC Derating
|
||
Ingress Protection
|
IP65
|
||
Noise Emission (Typical)
|
≤40 dB
|
||
Cooling Concept
|
Smart Cooling
|
||
Permissible Altitude (m)
|
4000
|
||
Warranty
|
5 Years
|
||
Grid Connection Standard
|
IEC 61727, IEC 62116, CEI 0-21, EN 50549, NRS 097, RD 140, UNE 217002,
OVE-Richtlinie R25, G99, VDE-AR-N 4105 |
||
Operating Surroundings Humidity
|
0-100%
|
||
Safety EMC / Standard
|
IEC/EN 61000-6-1/2/3/4, IEC/EN 62109-1, IEC/EN 62109-2
|
||
Features
|
|
||
Display
|
LCD1602
|
||
Interface
|
RS485/RS232/Wifi/LAN
|